Description
Delta DRL-12V240W1EN DIN Rail Power Supply 12VDC 20A 240W, Enclosed, Adj Vout, in: 90-264Vac
Output Voltage
12V
Output Power
240W
Output Current
20A
Input Voltage Range
90-264Vac
Dimensions (H x W x D)
123.6 x 40 x 116.8 mm
4.87” x 1.57” x 4.60”
Unit Weight
0.62 kg (1.37 lb)
Highlights & Features
- Universal AC input voltage range
- Built-in constant current circuit for reactive loads
- High power density
- Operate from -30°C to +70°C with -40°C Cold Start
- Reduced no-load power consumption
- Compliance with DOE VI Energy Standard
- Compliance to SEMI F47 @ 200Vac
Tech Specs
Output
Output Current 20A |
Output Voltage 12V |
Output Voltage Range 10.8-13.2Vdc |
Output Voltage Adjustment Range 10.8-13.2Vdc |
Output Power 240W |
Line Regulation ± 0.5% @ 115Vac & 230Vac |
Load Regulation ± 1.0% |
PARD < 120mVpp @ 0°C to +70°C < 360mVpp @ -30°C to 0°C |
Start-up Time 500ms typ. @ 115Vac & 230Vac |
Hold-up Time 20ms typ. @ 115Vac (100% load) 20ms typ. @ 230Vac (100% load) |
Dynamic Response (Overshoot & Undershoot O/P Voltage) ± 10% @ 115Vac & 230Vac input, 10-100% load (Slew Rate: 2.5A/μS, 50% duty cycle @ 5Hz & 10KHz) |
Start-up with Capacitive Loads 8,000µF Max |
Rise Time 30ms typ. @ 115Vac & 230Vac |
Input
Nominal Input Voltage 100-240Vac |
Input Voltage Range 90-264Vac |
Nominal Input Frequency 50-60Hz |
Input Frequency Range 47-63Hz |
Input Current 2.5A typ. @ 115Vac, 1.3A typ. @ 230Vac |
Efficiency at 100% load 86.5% typ. @ 230Vac |
Inrush Current 40A typ. @ 230Vac |
Power Factor at 100% load > 0.95 @ 115Vac & 230Vac |
Leakage Current < 0.75mA @ 240Vac |
Mechanical
Case Chassis / Cover Aluminum / SGCC |
Indicator Green LED (DC OK) |
Cooling System Convection |
Input Terminal 3 Pins (Rated 300V/30A) |
Output Terminal 4 Pins (Rated 300V/20A) |
Noise Sound Pressure Level (SPL) < 25dBA |
Mounting Rail Standard TS35 DIN Rail in accordance with EN 60715 |
Unit Weight 0.62 kg (1.37 lb) |
Additional Information
Stock Available Onehunga: |
0 |
Stock Available Wellington: |
0 |
Stock Available St Lukes: |
0 |